LV Switchboard Testing
IEC 60439-1 has several type tests. For ASTA certificates of complete type tests we need to perform each test. We can also issue Certificates covering just Short-circuit rating or temperature rise or dielectric properties.
As switchboard design varies a lot, we require advice on the overall size of the board, the rated current of the incoming unit and the size of each outgoing unit. A sketch of the front view of the board showing the units and the busbar run and a single line diagram is helpful.
For each test required we need advice on the following:
| Temperature rise | Test current of incoming and outgoing units and diversity factor |
| Dielectric properties | Rated operational voltage eg 415 V
Rated insulation voltage eg 690 V
Rated Impulse voltage eg 6 kV |
| Short circuit rating | Specify whether busbars and or units are to be tested
Short time current ratings of phase busbars eg 50 kA for 1s
Short time current ratings of Neutral circuit can be specified or performed at 60% |
| Degree of Protection | Need to specify the IP rating required eg IP32 or IP43 or IP2X etc |
| Protective earth circuit |  |
| Creepage and clearance |  |
| Mechanical operation | Quantity eg 5 units, 1000 operations per unit |
| |
|